RTM8248-GSM       RTM-FEM-GSM       RTM-RTR-GSM

RTM8248-GSM

CONTROL UNIT for Section Switch Remote Control (SSRC) and DSP

Purpose: Unit RTM8428-GSM performs scanning of analog and discrete values and operating power blocks of SSRC, DSP and similar devices. RTM8248-GSM
Power supply: 24 V DC (optionally 12 V DC, 48 V DC) 10 %
Consumption:
a) in no transmission state: 120 mA (230 mA, 60 mA)
b) in transmission state: 330 mA (650 mA, 170 mA)
Storage temperature: -40 C to +80 C
Operation temperature: -30 C to +65 C
Humidity: 0 % to 95 %
Communication with superior system: GPRS/GSM APN LAN (INTRANET)
Communication protocols: IEC 870-5-101
IEC 870-5-104
Digital inputs:  
Number of bits: 24
Galvanic isolation: disruptive strength 2,5 kV
ON voltage level: 12 V to 110 V (configurable ON and OFF ranges)
ON current level: 1 mA to 20 mA (configurable ON and OFF ranges)
Signal type: any compound of single and double bit for total amount of bits
Time processing: with adjustable time filter which determines minimal acceptable duration of changes
Digital relay outputs:  
Number of outputs: 8
Galvanic isolation: disruptive strength 1,5 kV
Max. current loading: 3 A
Max. switching voltage: 30 V DC (optionally 48 V DC)
Signal type: state
bistable
pulse (configurable pulse duration for each output)
Analog inputs:  
Number of inputs: 7
Inputs (configurable for each channel): DC voltage, negative pole on GND
range 0 V to 5 V (optionally 0 V to 10 V)
DC current, negative pole on GND
range 0 mA to 5 mA (optionally 0 mA to 20 mA)
Accurate class: 2,5 (optionally 1,5)
Resolution: 12 bits
Time processing: periodic
based on changes with filtering (configurable delta criterion for each input)
Weight: 550 g
Dimension: length 225 mm
  width 100 mm
  height 40 mm with antenna connector and DIN rail mounting bracket

 

RTM FEM GSM

MANAGING TELEMETRIC MODUL

Purpose: Unit RTM-FEM-GSM is a control telemetry module that communicates with a superior system via GSM / GPRS. For data communication protocol is done IEC 60870-5 - 104 Unit RTM-FEM-GSM includes optional up to 3 serial interfaces for communication with subordinate system. The unit RTM-FEM-GSM is possible using these serial interfaces to connect devices containing digital and analog inputs and outputs, so. expanders, devices communicating protocol IEC 60870-5-101 or any device using the transparent serial channel through TCP / IP. Unit RTM-FEM-GSM also includes an Ethernet interface for connecting subdivisional system using this interface and protocol IEC 60870-5-104. RTM-FEM-GSM
Power supply: 12 V DC/24V DC +/- 10%
Consumption:
a) in no transmission state @ 12 V: 350 ma
b) in active mode GSM 900 @12V: 700 mA
b) in active mode GSM 1800 @12V: 700 mA
Storage temperature: -40 C a +80 C
Operation temperature: -30 C a +65 C
Humidity: 0 % a 95 %
Communication with superior system: GPRS/GSM
Communication protocols: IEC 870-5-101
IEC 870-5-104
Interfaces:  
Serial interfaces:  
P1: RS232/RS422/RS485 , RS232 full UART
P2: RS232/RS422/RS485 , RS232 full UART
P3: RS232/RS422/RS485 , RS232 full UART
Ethernet interface:  
E1: 10/100 Mb/s FULL/HALF DUPLEX
Console:  
Interface: serial special
Parameters: 115200 Bb, 8 bit, 1 stopbit, parity none
Weight: 370 g
Dimension: length 160 mm
  width 100 mm
  height 40 mm with antenna connector and DIN rail mounting bracket

 

RTM RTR GSM

MANAGING TELEMETRIC MODUL

Purpose: Unit RTM-RTR-GSM is a control telemetry module that communicates with a superior system via GSM / GPRS. For data communication protocol is done IEC 60870-5 - 104 Unit RTM-RTR-GSM includes optional up to 2 serial interfaces for communication with subordinate system. The unit RTM-RTR-GSM is possible using these serial interfaces to connect devices containing digital and analog inputs and outputs, so. expanders, devices communicating protocol IEC 60870-5-101 or any device using the transparent serial channel through TCP / IP. Unit RTM-RTR-GSM also includes an 2 Ethernet interfaces for connecting subdivisional system using this interface and protocol IEC 60870-5-104. RTM-RTR-GSM
Power supply: 12 V DC/24V DC +/- 10%
Consumption:
a) in no transmission state @ 12 V: 350 ma
b) in active mode GSM 900 @12V: 700 mA
b) in active mode GSM 1800 @12V: 700 mA
Storage temperature: -40 C a +80 C
Operation temperature: -30 C a +65 C
Humidity: 0 % a 95 %
Communication with superior system: GPRS/GSM
Communication protocols: IEC 870-5-101
IEC 870-5-104
Interfaces:  
Serial interfaces:  
P1: RS232/RS422/RS485 , RS232 full UART
P2: RS232/RS422/RS485 , RS232 full UART
Ethernet interfaces:  
E1: 10/100 Mb/s FULL/HALF DUPLEX
E2: 10/100 Mb/s FULL/HALF DUPLEX
Console:  
Interface: serial special
Parameters: 115200 Bb, 8 bit, 1 stopbit, parity none
Weight: 285 g
Dimension: length 120 mm
  width 100 mm
  height 40 mm with antenna connector and DIN rail mounting bracket